Grid frequency exceeds the value range stated in accordance with Safety regulations
If it happens occasionally, it belongs to the short-time abnormality of the power grid, the inverter will return to normal operation after detecting the normal power grid, and there is no need to deal with it.
In case of frequent occurrence but automatic recovery, please confirm if the grid voltage is outside the permissible range due to local grid conditions, try to modify the values of the monitored operational limits after informing the electric utility company first.
If it cannot be recovered for a long time, please confirm:
The current exceeds 1Amp in stastic and 4Amp in dynamic
Disconnect the inverter from the utility grid and the PV array, and reconnect it after LED turns off. If this fault is still being displayed, please contact the service.
DSP failed to read from EEPROM
Disconnect the inverter from the utility grid and the PV array, and reconnect it after LED turns off. If this fault is still being displayed, please contact the service.
Duo Core – Master CPU abnormal communication with slave CPU
Disconnect the inverter from the utility grid and the PV array, and reconnect it after LED turns off. If this fault is still being displayed, please contact the service.
Voltage in bus-capacitor is greater than permissible value.
Check the open-circuit voltages of the strings and make sure it is below the maximum DC input voltage of the inverter.
If the input voltage lies within the permissible range while the fault occurs, please contact the service.
Bus-voltage is lower than standard Bus-voltage
Check the open-circuit voltages of the strings and make sure it is below the maximum DC input voltage of the inverter. If the input voltage lies within the permissible range while the fault occurs, please contact the service.
DRM switch S9 fault
Check the connection of DRM device. If the DRM device is connected normally while this fault occurs, please contact the service.
DRM switch S0 fault
Check the connection of DRM device. If the DRM device is connected normally while this fault occurs, please contact the service.
N-PE voltage higher than permissible value.
Check the connection of AC wires. Make sure the voltage of phase-to-phase, phase-to-netrue is right. If not, recorrect it.